Vulnerability Description
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
CVSS Score
HIGH
Affected Products
| Vendor | Product | Versions |
|---|---|---|
| Siemens | Ec 61850 System Configurator Firmware | < 5.80 |
| Siemens | Ec 61850 System Configurator | - |
| Siemens | Sicam Pq Analyzer Firmware | < 3.11 |
| Siemens | Sicam Pq Analyzer | - |
| Siemens | Sicam Scc Firmware | - |
| Siemens | Sicam Scc | - |
| Siemens | Digsi 4 Firmware | - |
| Siemens | Digsi 4 | - |
| Siemens | Digsi 5 Firmware | < 7.80 |
| Siemens | Digsi 5 | - |
| Siemens | Sicam Pas\/Pqs | < 8.11 |
Related Weaknesses (CWE)
References
- http://www.securityfocus.com/bid/105933Third Party AdvisoryVDB Entry
- https://cert-portal.siemens.com/productcert/pdf/ssa-159860.pdfVendor Advisory
- https://ics-cert.us-cert.gov/advisories/ICSA-18-317-01Third Party AdvisoryUS Government Resource
- http://www.securityfocus.com/bid/105933Third Party AdvisoryVDB Entry
- https://cert-portal.siemens.com/productcert/pdf/ssa-159860.pdfVendor Advisory
- https://ics-cert.us-cert.gov/advisories/ICSA-18-317-01Third Party AdvisoryUS Government Resource
FAQ
What is CVE-2018-4858?
CVE-2018-4858 is a vulnerability with a CVSS score of 7.8 (HIGH). A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All ve...
How severe is CVE-2018-4858?
CVE-2018-4858 has been rated HIGH with a CVSS base score of 7.8/10. Review the CVSS metrics above for detailed severity breakdown.
Is there a patch for CVE-2018-4858?
Check the references section above for vendor advisories and patch information. Affected products include: Siemens Ec 61850 System Configurator Firmware, Siemens Ec 61850 System Configurator, Siemens Sicam Pq Analyzer Firmware, Siemens Sicam Pq Analyzer, Siemens Sicam Scc Firmware.