MEDIUM · 6.8

CVE-2022-30316

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware up...

Vulnerability Description

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.

CVSS Score

6.8

MEDIUM

CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Attack Vector
PHYSICAL
Attack Complexity
LOW
Privileges Required
NONE
User Interaction
NONE
Scope
UNCHANGED
Confidentiality
HIGH
Integrity
HIGH
Availability
HIGH

Affected Products

VendorProductVersions
HoneywellSafety Manager Firmware-
HoneywellSafety Manager-

Related Weaknesses (CWE)

References

FAQ

What is CVE-2022-30316?

CVE-2022-30316 is a vulnerability with a CVSS score of 6.8 (MEDIUM). Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware up...

How severe is CVE-2022-30316?

CVE-2022-30316 has been rated MEDIUM with a CVSS base score of 6.8/10. Review the CVSS metrics above for detailed severity breakdown.

Is there a patch for CVE-2022-30316?

Check the references section above for vendor advisories and patch information. Affected products include: Honeywell Safety Manager Firmware, Honeywell Safety Manager.