Vulnerability Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
CVSS Score
HIGH
Affected Products
| Vendor | Product | Versions |
|---|---|---|
| Hitachienergy | Rtu500 Firmware | 13.3.1 |
| Hitachienergy | Rtu500 | - |
Related Weaknesses (CWE)
References
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=e
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=
FAQ
What is CVE-2022-4608?
CVE-2022-4608 is a vulnerability with a CVSS score of 7.5 (HIGH). A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with sup...
How severe is CVE-2022-4608?
CVE-2022-4608 has been rated HIGH with a CVSS base score of 7.5/10. Review the CVSS metrics above for detailed severity breakdown.
Is there a patch for CVE-2022-4608?
Check the references section above for vendor advisories and patch information. Affected products include: Hitachienergy Rtu500 Firmware, Hitachienergy Rtu500.